DM 811 – Absolute Pressure Input

    • Absolute pressure input
    • PT100 temperature input
    • 8 digital inputs (+24 V DC/3.7 mA/0.5 ms)

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Request a Quote
SKU: DM 811 - Absolute Pressure Input Categories: , , , , Brand:

Description

    • Absolute pressure input
    • PT100 temperature input
    • 8 digital inputs (+24 V DC/3.7 mA/0.5 ms)

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Technical Data

 

Digital Inputs

Type standard
Number 8
Input voltage +24 V DC (+18-30 V DC)
Input current 3.7 mA at +24 V
Input delay typically 0.5 ms

Analog Inputs

Type temperature
Number 1
Resolution 0.1 °C
Sensor types PT100
Measurement range 0 … 300 °C or 100,0 – 212,1 Ω
Measurement precision ±0.5 % of maximum measurement value
Conversion time per channel 1 ms
Cable break monitor Yes
Hardware filter typically 1 kHz, low pass 3rd order
Software filter configurable

Pressure Sensor

Number 1
Pressure sensor type absolute pressure
Measurement range 0-1600 mbar
Measurement value 0-16000
Resolution 12 bits
Conversion time for all channels 1 ms
Hardware filter typically 1 kHz, low pass 3rd order
Software filter configurable
Measurement precision ±0.25 % of scale end value, i.e. ±4.0 mbar for 25 °C ambient temperature with offset and gain comparison; ±1.00 % of scale end value, i.e. ±16.0 mbar for 0-50 °C ambient temperature without offset and gain comparison

Mechanical Features

Dimensions 25 x 104 x 72 mm (W x H x D)
Protection type IP20

Article Number/Certification

Article number 20-008-811
Standardization/­certification UL 508 (E247993)