Description
- 2 analog inputs (0-20 mA/16 bits) for measuring current
- Reference voltage (+10 V DC/10 mA)
- Processed signals on the diagnostic connector measurable (not calibratable)
Analog Inputs |
|
Type | Current |
Number | 2 |
Resolution | 16 bits |
Measurement range | 0-20 mA |
Measurement precision | typically ±0.027 % |
Conversion time per channel | ≤ 25 µs |
Galvanic isolation | Yes |
Reference Output |
|
Reference voltage | +10 V DC |
Allowable output current | 10 mA |
Short-circuit proof, current limited | Yes |
Accuracy | typically ±0.01 % maximum ±0.05 % |
Mechanical Features |
|
Dimensions | 42.2 x 27 x 91.3 mm (W x H x D) |
Protection type | IP00 |
Article Number/Certification |
|
Article number | 18-001-222 |
Reviews